A real machine is not one long list of rungs. IEC 61131-3 gives you three tools to keep it readable, and PLC-Ladder compiles, draws and simulates all three. This page walks through a small conveyor line built with them; you can open it in the workbench and run its tests.

1 · Programs (POUs) split the machine into parts

A program organisation unit (POU) is one PROGRAM, FUNCTION_BLOCK or FUNCTION. Give each part of the machine its own program: here the line has Infeed, Station and Outfeed, each with its own inputs and outputs (declared with addresses such as %IX0.0) and its own ladder.

2 · Function blocks: define once, use per device (Rockwell: AOI)

What Rockwell calls an add-on instruction (AOI) is a function block: logic plus its own memory, defined once and instantiated once per device. MotorBlock holds a start / stop seal-in, an interlock, a running-feedback timer that latches a fault, and a SimMode input that makes the feedback follow the command so the line can be simulated without real contactors. All three programs use it, each with its own instance.

TYPE ConveyorStatus :
STRUCT
    Running : BOOL;
    Fault : BOOL;
    Parts : INT;
END_STRUCT
END_TYPE

FUNCTION_BLOCK MotorBlock
VAR_INPUT
    StartCmd : BOOL;     (* start request: pushbutton, HMI or sequence *)
    StopCmd : BOOL;      (* stop request *)
    Interlock : BOOL;    (* TRUE = permitted to run (E-stop, guards, overload) *)
    Feedback : BOOL;     (* running feedback from the contactor auxiliary *)
    SimMode : BOOL;      (* TRUE in simulation: the feedback follows Run *)
    Reset : BOOL;        (* clears a latched fault *)
    FeedbackTime : TIME; (* how long the feedback may take, e.g. T#2s *)
END_VAR
VAR_OUTPUT
    Run : BOOL;          (* the contactor coil *)
    Running : BOOL;      (* Run confirmed by the feedback *)
    Fault : BOOL;        (* no feedback in time, latched until Reset *)
END_VAR
VAR
    FeedbackTimer : TON;
END_VAR
Run := (StartCmd OR Run) AND NOT StopCmd AND Interlock AND NOT Fault;
Running := Run AND (Feedback OR SimMode);
FeedbackTimer(IN := Run AND NOT (Feedback OR SimMode), PT := FeedbackTime);
Fault := (FeedbackTimer.Q OR Fault) AND NOT Reset;
END_FUNCTION_BLOCK

3 · User data types (UDTs): group what belongs together

A TYPE ... STRUCT groups related signals. Every program here keeps a ConveyorStatus with Running, Fault and Parts, reached member by member (Status.Parts := PartCounter.CV;). The ladder and the Signals panel show the dotted names, and an HMI connected over OPC UA sees nodes such as Status.Running.

PROGRAM Station
VAR
    RunCmd AT %IX1.0 : BOOL;
    PartSensor AT %IX1.1 : BOOL;
    CountReset AT %IX1.2 : BOOL;
    StationMotor AT %QX1.0 : BOOL;
    Motor2 : MotorBlock;
    PartCounter : CTU;
    Status : ConveyorStatus;
END_VAR
// the same MotorBlock again: one definition, one instance per belt
Motor2(StartCmd := RunCmd, StopCmd := NOT RunCmd, Interlock := TRUE, Feedback := FALSE,
       SimMode := TRUE, Reset := FALSE, FeedbackTime := T#2s);
StationMotor := Motor2.Run;
PartCounter(CU := PartSensor AND Motor2.Run, RESET := CountReset, PV := 100);
Status.Running := Motor2.Running;
Status.Fault := Motor2.Fault;
Status.Parts := PartCounter.CV;
END_PROGRAM

4 · Tests that prove it

The example comes with scenario tests that the simulator runs on every change:

  • Infeed: Start runs the infeed motor, it keeps running when Start is released, and Stop stops it.
  • Station: The station motor follows RunCmd.
  • Station: Parts are counted only while the station motor runs; CountReset clears the count.
  • Outfeed: A full outfeed stops the belt, and Start does not restart it until the outfeed clears.

What is supported, exactly

Function blocks: inputs, outputs and local variables, timers, counters and other blocks inside, no recursion and no VAR_IN_OUT. Structs: members BOOL, INT, DINT, REAL, TIME or a one-dimensional array of those, one level of nesting, used member by member (not inside function blocks yet). Anything else is refused with the line and the reason, never converted wrongly.